Slow the load.
Cube the saving.
On suitable variable-torque pumps, fans and blowers, reducing speed can reduce required shaft power approximately with the cube of speed. Drag the frequency control and watch flow, pressure, power and motor current respond differently.
P₂ / P₁ = (n₂ / n₁)³(40 / 50)³ = 51.2%Flow follows speed. Pressure follows speed squared. Power follows speed cubed.
The motor still needs flux-producing current. The current gauge therefore does not follow the cube-law power bar.
Fill the same tank: DOL versus VFD
A 10 m³ process tank is filled from empty. The DOL pump runs at 50 Hz. Drag the VFD control before or during the test: the water level and accumulated energy will not reset.
DOL pump 50 Hz · full speed
VFD pump 40.0 Hz · 80.0% speed
Illustrative assumptions: 10 m³ tank, 20 m³/h full-speed flow, 15 kW full-speed shaft power and a friction-dominated system where flow follows speed and power follows speed cubed. The animation is accelerated. For a real tank with significant or changing static head, use the manufacturer’s pump curve and the actual system curve.
What could a £350 drive save?
This worked example compares the 15 kW DOL pump with an assumed Siemens SINAMICS V20 drive. It applies the ideal affinity laws to the same 10 m³ tank and shows how the longer fill time affects the energy used for each completed tank.
power ∝ speed³, but fill time ∝ 1/speed. Therefore energy per tank = 7.5 × (Hz ÷ 50)² kWh.| VFD speed | Fill time | Energy per fill | Energy saved per fill | Saving per day | Saving per year | £350 payback |
|---|---|---|---|---|---|---|
| 50 Hz | 30.0 min | 7.50 kWh | 0.00 kWh | £0.00 | £0 | — |
| 45 Hz | 33.3 min | 6.08 kWh | 1.43 kWh | £1.78 | £650 | 197 days |
| 40 Hz | 37.5 min | 4.80 kWh | 2.70 kWh | £3.38 | £1,232 | 104 days |
| 35 Hz | 42.9 min | 3.68 kWh | 3.83 kWh | £4.78 | £1,745 | 73 days |
| 30 Hz | 50.0 min | 2.70 kWh | 4.80 kWh | £6.00 | £2,190 | 58 days |
| 25 Hz | 60.0 min | 1.88 kWh | 5.63 kWh | £7.03 | £2,566 | 50 days |
| 20 Hz | 75.0 min | 1.20 kWh | 6.30 kWh | £7.88 | £2,874 | 44 days |
Theoretical figures only. Annual savings assume five fills every day for 365 days. Payback covers the assumed £350 drive price only and excludes installation, controls, commissioning and maintenance. Actual savings will be affected by drive and motor losses, pump efficiency, minimum safe speed and especially static head. A real project must be checked against the pump and system curves.
For the same suitable pump, fan or blower, flow is approximately proportional to rotational speed: Q₂/Q₁ = n₂/n₁.
Pressure or pump head is approximately proportional to speed squared: H₂/H₁ = (n₂/n₁)².
Shaft power is approximately proportional to speed cubed: P₂/P₁ = (n₂/n₁)³. A small speed reduction can therefore produce a much larger power reduction.
Technical basis: ABB guide to variable-speed drives and motors · Danfoss Facts Worth Knowing about AC Drives. Values on this page are illustrative, not a drive-selection calculation.